- Anti-static floor mat construction methods and related requirements are introduced
-
Issue time:2022-02-24 10:56:10 source:安珂地墊 views:4336
The reason why anti-static floor mats have anti-static effect lies in its composition of raw materials. This synthetic rubber is mainly composed of materials with anti-static and dissipative static functions. The thickness of this double-layer composite structure is 2mm, the thickness of the surface layer of dissipative static layer is about 0.5mm, the thickness of the bottom conductive layer is about 1.5mm. the construction method of antistatic mats will also affect the antistatic effect, so users should also do a good job of construction supervision, follow the construction requirements and take the correct construction method.
Anti-static floor mats construction methods and construction requirements are as follows.
1. in the laying of antistatic mats before the good ground treatment.
?、?The foundation ground can be ground with water, porcelain ground, wooden floor.
?、?The ground should be flat, there can be no obvious unevenness, not more than five thousandths. During construction, it needs to be leveled gradually with leveling instrument to ensure the anti-static effect.
?、跿he ground should be strong enough, no sand and shelling, which needs to choose the right floor material.
?、躎he ground should be dry, if necessary, do a good job of drying treatment.
2、The construction procedure and specific method of antistatic floor mat.
?、貱leaning the ground. Cleaning equipment for the cleaning machine, cleaning agent selection 120 # gasoline or xylene, the purpose is to clean the ground impurities.
② ground laying materials for copper or aluminum strip, mainly used to dissipate static electricity, of which the copper strip 0.02mm thick, 30mm wide, the number of strips according to the actual ground laying needs to determine the length and number, while one end of the copper strip led to the earth.
?、?After doing the work of laying the ground network, you need to keep the ground dry, which is to ensure the effect of the application of conductive adhesive. Before laying the antistatic floor mat, you need to feel the conductive rubber with your hands, if it is not sticky, it represents its qualification. In practice, generally wipe to dry 20-30 minutes after the next step can be carried out. Anti-static mat bottom (black surface) operation is the same (coated conductive agent once can be), then the anti-static mats and ground bonding, and then heavy roller rolling 5 times, the surface of the anti-static rubber plate flattened a little, at room temperature for 48 hours can be used.
?、躎he ambient temperature during construction requires not less than 25℃, not too much humidity, and good ventilation.
?、軨onductive adhesive resistance coefficient is not more than 108Ω, peel strength Kg/2.5cm.
?、轈onductivity between the pores, the use of coated conductive adhesive can be, can also be affixed to the surface of the copper strip.
Anti-static floor mat construction is simple, but there are many details that need attention, users need to pay attention to each link to ensure the anti-static effect of the indoor environment.